dc.description.abstractIn the present study, optimization of PCM layer thickness and melting temperature to increase the energy-saving potential of the office building located in eight cities in the Cfb climate zone was conducted using the Fanger model. The sensitivity of the energy savings to the selection of PCM melting temperature was quantitatively analyzed using a novel indicator of average savings drop. Additionally, the investigation of the effect of real PCMs on the energy performance of the building located in Cfb climate as well as the economic and environmental analyses were accomplished. The results showed that the PCM layer with a thickness of 2 cm reached the highest values of energy savings per unit thickness. The optimization of the PCM melting temperature revealed that PCM 22–25 were optimum for the whole Cfb climate zone and resulted in energy consumption reduction values of up to 37.6%. The sensitivity analysis showed that the steadiness of the outdoor climate conditions affects the sensitivity of the energy savings to the selection of PCM melting temperature. The analysis of real PCMs revealed that PCM 25-r demonstrated more efficient performance in all cities. Overall, it was concluded that the integration of PCM can be considered an economically and environmentally feasible solution.en_US
dc.identifier.citationBozzhigitov, A., Memon, S. A., & Adilkhanova, I. (2022). Sensitivity of energy performance to the selection of PCM melting temperature for the building located in Cfb climate zone. Energy Reports, 8, 6301–6320. https://doi.org/10.1016/j.egyr.2022.04.059en_US
dc.identifier.urihttp://nur.nu.edu.kz/handle/123456789/6910
dc.language.isoenen_US
dc.publisherEnergy Reportsen_US
dc.rightsAttribution-NonCommercial-ShareAlike 3.0 United States*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-sa/3.0/us/*
dc.subjectType of access: Open Accessen_US
dc.subjectPhase change materials (PCM)en_US
dc.subjectCfb climate zoneen_US
dc.subjectFanger predictive mean vote indexen_US
dc.subjectEnergy consumption reduction (ECR)en_US
dc.subjectAverage savings drop (ASD)en_US
dc.titleSENSITIVITY OF ENERGY PERFORMANCE TO THE SELECTION OF PCM MELTING TEMPERATURE FOR THE BUILDING LOCATED IN CFB CLIMATE ZONEen_US
dc.typeArticleen_US
workflow.import.sourcescience

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
1-s2.0-S2352484722008241-main.pdf
Size:
4.1 MB
Format:
Adobe Portable Document Format
Description:
article

Collections