Impulse voltage distribution and frequency response of intershield windings
Loading...
Date
Authors
Bagheri, Mehdi
Phung, B. T.
Salay Naderi, Mohammad
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE Electrical Insulation Magazine
Abstract
Impulse voltage distributions in continuous disk windings are nonlinear, due to the small series capacitance of the winding. Consequently, transformer manufacturers often design large power transformers with interleaved windings to increase series capacitance, but in doing so reduce the value of the initial impulse voltage distribution coefficient α given by α = √(Cg/Cs), (1) where Cg is the shunt capacitance and Cs is the series capacitance of the winding. Sometimes fully interleaved windings are employed because they are more reliable, ensuring that the transformer will operate properly under lightning strike.
Description
Citation
Bagheri, M., Phung, B. T., & Naderi, M. S. (2016). Impulse voltage distribution and frequency response of intershield windings. IEEE Electrical Insulation Magazine, 32(5), 32-40. [7552374]. DOI: 10.1109/MEI.2016.7552374
Collections
Endorsement
Review
Supplemented By
Referenced By
Creative Commons license
Except where otherwised noted, this item's license is described as Attribution-NonCommercial-ShareAlike 3.0 United States